7.3.17 Control management
Each GPO can sink a current of up to 300mA maximum in the closed state and can accept up to 48V in the
opened state. The courant leakage is less than 1µA when opened and the resistance is less than 2 ohms when
closed. The GPO can be reset to its default values.

The opcally isolated GPI allows the user to drive the device externally.
There are two pins: one posive and one negave. The way to trigger it is to provide a current (10mA/3V min
and 45mA/24V max). The GPI is protected over polarity inversion.
There are two acvaon polaries: the input can be acve when powered or when unpowered.
The mode can be :
manual, not linked to an acon, driven by automaon
when input is acve, a TAKE is generated on one or several screens.
The GPI can be reset to its default values.